i-on160 The System Bus
Page 21
Figure 8. Zone Numbering with EXR-30.
Note how the EXPR-30 takes three consecutive bus device addresses, and the
zone numbers occupy a contiguous block of 30.
Adding/Removing Expanders and Zone Numbering
At some point after the initial installation you may wish to replace one of the
expanders:
You can replace an EXPR-30 with up to three EXPR-10 or EXPW-10
expanders. The control unit will use the three bus device numbers that were
allocated to the EXPR-30.
If you wish to add an EXPW-30 but there are not three spare device
numbers next to each other, then the control unit will not let you add the
device.
Zone 000
Connection point P0<00<00 (the first zone terminal on the control unit pcb) is
available for use as a valid zone. However, please note that SIA and CID
cannot report any alarms on zone 000. Cooper Security suggest that you might
find this zone useful as a Log Only zone.
MENU
A
B
1
4 ghi
7 pqrs
*
0
#
2 abc
5 jkl
3 def
6 mno
8 tuv 9 wxyz
MENU
A
B
1
4 ghi
7 pqrs
*
0
#
2 abc
5 jkl
3 def
6 mno
8 tuv 9 wxyz
MENU
A
B
1
4 ghi
7 pqrs
*
0
#
2 abc
5 jkl
3 def
6 mno
8 tuv 9 wxyz
K1-51
W1-01
Zone 20 -> R1<02<00
...
Zone 49 -> R1<02<29
EXPR-30
EXPW-10
R1-02,03,04
Zone 10 -> W1<01<00
...
Zone 14 -> W1<01<04
detectors
Zone 1 -> P0<00<01
...
Zone 4 -> P0<00<04
K1-52 K1-53
Komentáře k této Příručce