4. Programming
496964 Page 107
Notes:
1. If Command 143, option 1 is selected, all messages with a CID Code
are sent. If option 0 is selected, the restores marked with ‡ are not sent.
2. The control unit logs an Anti-Mask event to the zone number one
below that assigned the Anti-Mask type. See page 62 for an explanation
of the Anti-Mask zone type.
132: Send Tampers as Burglary
Some ARCs experience problems if a control unit sends "restore" messages
using SIA, wrongly interpreting them as "user restores". When using SIA
reporting, Command 132 enables you to program the control unit to send
tampers as alarms.
Option
0 (Default) The control unit sends all SIA messages as specified in
Command 131.
1 For full alarm response, the control unit sends tampers as burglary
(BA) and sends Contact ID 130 in place of Contact ID 137.
133: Do not Send SIA Restores
Use this command to stop the system sending SIA restore messages.
Option
0: SIA Restores Off (default). System does not send SIA restore
messages: FR (Fire Restore), PR (Panic Restore), UR (Technical
Restore), BR (Burglary Restore) or TR (Tamper Restore).
1: SIA Restores On. System sends SIA restore messages.
134 to 142: Not used
These commands are not used.
143: Contact ID Report Restores
If the Reporting Type is set to Contact ID (Command 103, option 1), use this
Command to select the types of contact ID messages that will be sent.
Option
0 Basic: all the messages with numbers in the "CID Code" column of the
table in "131: SIA Report Mode", except for those marked with an "‡".
1 Basic + Restore: all the messages with numbers in the "CID Code"
column of the table in "131: SIA Report Mode".
Note: If the keypad display shows "Custom" when you enter Command 143,
Downloader has been used to program Contact ID Report Restores.