Cooper Security 9751 Instalační manuál

Procházejte online nebo si stáhněte Instalační manuál pro Bezpečnostní systémy pro řízení přístupu Cooper Security 9751. Cooper Security 9751 Unit installation Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 148
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků

Shrnutí obsahu

Strany 1

INSTALLATION AND PROGRAMMING GUIDE HARDWIRED CONTROL UNITS

Strany 2

1. Introduction Page 2 496964 Features of the Control Unit All Models Control units in the 9x5x series provide: ° A four-wire bus connection for key

Strany 3 - Contents

4. Programming Page 92 496964 87: Keypad Dual Key Alarms This Command enables users to raise an alarm by pressing two keys on the keypad at the same

Strany 4

4. Programming 496964 Page 93 98: Load Full Defaults Use this Command to load default values for all Commands. 1. Enter programming mode (if you

Strany 5

4. Programming Page 94 496964 101: Call Mode You may select one of the following call modes: Option 0 Disabled. The control unit does not use any co

Strany 6

4. Programming 496964 Page 95 103: Reporting Type The system supports several message formats for communications: Option 0 Scancom Fast Format (F

Strany 7 - List of Figures

4. Programming Page 96 496964 To make static test call at regular intervals, you have two options: Cnn To make a static test call every nn hours, pre

Strany 8 - Page vi 496964

4. Programming 496964 Page 97 108: Dynamic Test Call With dynamic testing, the control unit makes a test call 24 hours after the last communicatio

Strany 9 - 1. INTRODUCTION

4. Programming Page 98 496964 111: Modem Speed (9851 only) Use this command to set the speed of the modem inside the 9851 (built-in communicator). Op

Strany 10 - Features of the Control Unit

4. Programming 496964 Page 99 114: Access Mode You may wish to impose extra security on communication between a remote PC and the control unit as,

Strany 11 - 496964 Page 3

4. Programming Page 100 496964 To enter a telephone number: 1. Enter programming mode (if you are not already there). 2. Key in 115 (or 116) Y at

Strany 12 - Elements of the IAS

4. Programming 496964 Page 101 118 and 119: Downloader Telephone Numbers Use these Commands to program the telephone numbers that the communicator

Strany 13 - 496964 Page 5

1. Introduction 496964 Page 3 9751 The 9751 provides: ° On-board connections for eight Fully Supervised Loop (FSL) zones or eight Closed Circuit

Strany 14 - Page 6 496964

4. Programming Page 102 496964 122: Communication Acknowledge This Command is available only if Country is set to Ireland (Command 0, option X1). In

Strany 15 - Expanders

4. Programming 496964 Page 103 126: Select Language The control unit can display messages on the keypads in several languages. Select option for th

Strany 16 - Page 8 496964

4. Programming Page 104 496964 129: Telecommand Requires Entry for Unset If the system is fitted with a radio expander, the user can use a telecomman

Strany 17 - User Control

4. Programming 496964 Page 105 BASIC Event SIA Code CID Code ALARM CONFIRM BV 139 BURG BA 130 BURG RESTORE BR 130‡ DURESS HA 121 EXIT TIMEO

Strany 18 - Page 10 496964

4. Programming Page 106 496964 TELCO1 FAULT RESTORE LR - ZONE OMIT BB 573 SUMMARY Event SIA Code CID Code AC LOST AT 301 AC RESTORE AR 30

Strany 19 - 2. TECHNICAL DESCRIPTION

4. Programming 496964 Page 107 Notes: 1. If Command 143, option 1 is selected, all messages with a CID Code are sent. If option 0 is selected, the

Strany 20 - Outputs

4. Programming Page 108 496964 144 to 150: Not used These commands are not used. 151 to 158: Plug-by Communicator Outputs The main circuit board of t

Strany 21 - Control Unit PCB Layouts

4. Programming 496964 Page 109 Note: 1. If the control unit is using Fast Format signalling, and has sent a Burg to the ARC, the control unit activ

Strany 22 - Page 14 496964

4. Programming Page 110 496964 162: External Sounder on Confirmed or Unconfirmed Alarm Note: Enable Alarm Confirmation (Command 89) to access this Co

Strany 23 - 496964 Page 15

4. Programming 496964 Page 111 Option 0 User/Engineer. The user can reset the system after a first alarm but an engineer is required to reset the

Strany 24 - Page 16 496964

1. Introduction Page 4 496964 Elements of the IAS An IAS comprises a control unit in a shielded case, with one to four separate keypads and various d

Strany 25 - 496964 Page 17

4. Programming Page 112 496964 Notes: 1. Generating a pulse on an output depends both on a set or unset pulse being defined for the output and on th

Strany 26 - Radio Expander PCB Layouts

4. Programming 496964 Page 113 180: Print Log (9851 only) This Command instructs the control unit to print the event log through the serial port on

Strany 27 - 9960 Radio Expander

4. Programming Page 114 496964 185: Keyswitch Auto Reset This Command instructs the control unit to reset a tripped keyswitch zone automatically if t

Strany 28 - Page 20 496964

4. Programming 496964 Page 115 191 to 198: Fast Format Channels If Fast Format reporting is selected (Command 103, option 0) Commands 191 to 198 al

Strany 29 - 3. INSTALLATION

4. Programming Page 116 496964 200: Forbikobler Entry Timer This Command sets the interval between a user entering the premises through a Forbikobler

Strany 30 - Page 22 496964

4. Programming 496964 Page 117 Setting Different Entry Timers for Different Entrances Suppose that you have installed a system on a site that can b

Strany 31 - Fitting the System

4. Programming Page 118 496964 Using a Partitioned System Introduction When programming a control unit, there are two ways of changing from a single

Strany 32 - Page 24 496964

4. Programming 496964 Page 119 Programming Partitions Once you have selected a partitioned system, you can use the following Commands to program ea

Strany 33 - 496964 Page 25

4. Programming Page 120 496964 Differences in Commands for Partitioned Systems When you are using a partitioned system, some Commands offer new optio

Strany 34 - Wiring the Control Unit

4. Programming 496964 Page 121 Common Areas Setting up a Common Area You can create a common area linked to two or more partitions. The system sets

Strany 35 - Keypads

1. Introduction 496964 Page 5 1. 725r EUR PA 9. 9954 hardwired expander 2. 726r EUR PA 10. Passive Infra Red detectors 3. 715r EUR wirefree P

Strany 36 - Page 28 496964

4. Programming Page 122 496964 To see how this works, start with what happens at the end of a working day when all the users leave the building. User

Strany 37 - 496964 Page 29

4. Programming 496964 Page 123 LobbyCommon AreaOffice APartition AOffice BPartition BKPD KPDZ1Z2Z3Z4 Figure 38. Using a Private Door Partition A ha

Strany 38 - Connecting Detector Circuits

4. Programming Page 124 496964 Example 2. Double Common Area You are not limited to having one common area. Figure 40 shows three partitions sharing

Strany 39 - 496964 Page 31

4. Programming 496964 Page 125 Partition D remains set during the day. Partitions A, B and C are unset, so the control unit leaves the common area

Strany 40 - Connecting Expanders

4. Programming Page 126 496964 ACPO DD243: 2002 Compliance Applicability Please study this section if all of the following apply: 1. You are install

Strany 41 - Addressing Expanders

4. Programming 496964 Page 127 The table below summarises which options to select on various Commands in order to comply with paragraphs 6.4.2 to 6

Strany 42 - Programming Outputs

4. Programming Page 128 496964

Strany 43 - Communicator

496964 Page 129 5. TESTING 90: Reading the Event Log The control unit keeps a log of recent events. The log can contain up to 250 events. Each event

Strany 44 - Page 36 496964

5. Testing Page 130 496964 To print a listing of the control unit's configuration, key in 90 8 Y. Note: 975x models do not have the connector re

Strany 45 - Statutory Information

5. Testing 496964 Page 131 Keypad Display Printed (9851 only)* Meaning Knn Tamper Tamper K/P KEYPAD Tamper alarm on keypad nn Tamper Knn Restr

Strany 46 - Safety Notice

1. Introduction Page 6 496964 Keypad Figure 2. 9930 Keypad The 9930 keypad has a 16-character Liquid Crystal Display (LCD) that shows "first to

Strany 47 - 496964 Page 39

5. Testing Page 132 496964 Keypad Display Printed (9851 only)* Meaning Telecmmd PA Telecmd Panic PA started from PA Test Call Man Trig Test Tes

Strany 48 - Page 40 496964

5. Testing 496964 Page 133 97: Engineer Walk Test This function enables the engineer to test all devices on the system. 1. Enter programming mode.

Strany 49

5. Testing Page 134 496964

Strany 50 - Page 42 496964

496964 Page 135 Index 24-hour Alarm ... 90 9751 PCB layout ...

Strany 51 - 496964 Page 43

Index Page 136 496964 Dual reporting...94 Duration bell ...

Strany 52 - Initial Start Up

Index 496964 Page 137 exit time ... 88 Line line fault input ...

Strany 53 - 496964 Page 45

Index Page 138 496964 defaults ...58 report restores...

Strany 54 - Page 46 496964

Declaration of Conformance Cooper Security Ltd issues this certificate to certify that the equipment known as: 9751/9752/9851 Complies with the f

Strany 56 - Page 48 496964

1. Introduction 496964 Page 7 If the Dual Key Alarm function is enabled (Command 87), users can trigger an alarm by pressing the following pairs o

Strany 57 - 496964 Page 49

1. Introduction Page 8 496964 Radio Expanders Radio expanders enable you to connect wirefree devices to the control unit. They can work with the foll

Strany 58 - Page 50 496964

1. Introduction 496964 Page 9 Partitioned or Single System During installation, the Installer can organise security levels A to D as a partitioned

Strany 59 - 496964 Page 51

1. Introduction Page 10 496964

Strany 60 - Page 52 496964

496964 Page 11 2. TECHNICAL DESCRIPTION Control Unit Specification General Environmental Grade 1 (975x) Grade 2 (9851) Operating temperature -1

Strany 61 - 496964 Page 53

9851, 9752, 9751 Hardwired Control Unit Installation and Programming Guide This document applies to control panels using software version 2.04.nnnn.

Strany 62 - Page 54 496964

2. Technical Description Page 12 496964 Standby battery (not supplied) 12V rechargeable lead-acid, gel-type battery. Low battery voltage cutoff = 10

Strany 63 - 496964 Page 55

2. Technical Description 496964 Page 13 Fuses The 9751 and 9752 use two fuses for overcurrent protection: F1 – 12V AUX output F-1A F2 – battery

Strany 64 - Performing an Engineer Reset

2. Technical Description Page 14 496964 BATT F-2A12V AUXF-1A1141312111098762345 1. Outputs (RELAY OUTPUTS not used) 8. Plug-by (standalone) communi

Strany 65 - Re-entering Programming Mode

2. Technical Description 496964 Page 15 BATT F-2A12V AUXF-1A234567891011121314151 1. Outputs (OP1 and OP2 not used) 9. Plug-by (standalone) c

Strany 66 - Page 58 496964

2. Technical Description Page 16 496964 169 1. Lid tamper connector 10. Telephone line terminals for built-in communicator2. Zone connectors 11. L

Strany 67 - Adding and Deleting Tags

2. Technical Description 496964 Page 17 9954 Hardwired Expander PCB Layout The 9954 hardwired expander provides connectors for eight CCL, FSL or

Strany 68 - To Delete a Tag

2. Technical Description Page 18 496964 Radio Expander PCB Layouts The 9955, and its replacement the 9960, are Class VI radio expanders. Class VI is

Strany 69 - 0: Country PTT Defaults

2. Technical Description 496964 Page 19 9960 Radio Expander The 9960 radio expander supports eight or sixteen wirefree zones, depending on the m

Strany 70 - Page 62 496964

2. Technical Description Page 20 496964

Strany 71 - 496964 Page 63

496964 Page 21 3. INSTALLATION Caution: Always remove mains power before opening the case lid. Do not work inside the control unit with mains power

Strany 72 - Page 64 496964

496964 Page i Contents 1. INTRODUCTION...1 About this Manual

Strany 73 - 496964 Page 65

3. Installation Page 22 496964 Cabling Keypads and Expanders Cooper Security recommends that you use 8-core 7/0.2 or 16/0.2 alarm cable for wiring ke

Strany 74 - Page 66 496964

3. Installation 496964 Page 23 When carrying out the cabling, there are two important points to remember: 1. Do not connect anything other than ke

Strany 75 - 496964 Page 67

3. Installation Page 24 496964 6. Mount the front cover of the keypad (containing the keypad PCB) onto the backplate and make sure that the tamper s

Strany 76 - 20: Change Engineer Code

3. Installation 496964 Page 25 Figure 12. Fitting a 934 Module (in position) 3. Secure the module in position with a screw through the lug in th

Strany 77 - 23: Remote Reset

3. Installation Page 26 496964 Wiring the Control Unit Cable Entries The control unit case back provides several cable entries. It is designed to sta

Strany 78 - Page 70 496964

3. Installation 496964 Page 27 Keypads Keypad Addressing The control unit is supplied with one keypad. If you have fitted more keypads, each one m

Strany 79 - 31: Zone Tamper Reset

3. Installation Page 28 496964 Connecting Entry/Exit Devices and External Sounders Figures 16 and 17 show the connections for keypads, Exit Terminate

Strany 80 - 34: PA Reset

3. Installation 496964 Page 29 Bell StrobeBell-ve Tamper Return-ve Hold Off+ve Hold Off-ve Apply trigTypical SAB4-core9930 Keypad-ve+ve0V 12V

Strany 81 - 38: System Tamper Reset

3. Installation Page 30 496964 Connecting Detector Circuits The connectors for the detector circuits, or zones, are on the left hand edge of the main

Strany 82 - Page 74 496964

3. Installation 496964 Page 31 FSL Connections The control unit provides enough connectors for 8 (975x) or 16 (9851) FSL zones. If you wish to con

Strany 83 - 40: System Auto Rearm

Contents Page ii 496964 Summary of Programming Commands ...

Strany 84 - 43: Level A Entry Time

3. Installation Page 32 496964 EOL Connections (9851 only) Each EOL zone is a two-wire closed loop that uses a single 2K2 resistor fitted in series w

Strany 85 - 46: Tamper Alarm Response

3. Installation 496964 Page 33 Note: Make sure that the control unit and the expander use the same wiring method for zones. If you select a differ

Strany 86 - 50: CSID Code

3. Installation Page 34 496964 Programming Outputs Control unit panel outputs can be programmed using the commands shown in the table below. The open

Strany 87 - 53: Abort Reset

3. Installation 496964 Page 35 Wiring a Keyswitch Interface Figure 27 shows the connections for a 9928 Keyswitch Interface. You can fit only one k

Strany 88 - 55: Not used

3. Installation Page 36 496964 The communicator can be used for: • Transmitting alarm signals to alarm receiving equipment at a central monitoring s

Strany 89 - 59: External Sounder Tamper

3. Installation 496964 Page 37 Statutory Information Applications The built-in communicator is suitable for connection to the following types of n

Strany 90 - 64: Level B Entry Time

3. Installation Page 38 496964 Safety Notice Figures 28 and 29 identify connectors for Safety Extra-Low Voltage (SELV) and Telecommunications Network

Strany 91 - 67: Forbikobler Approved

3. Installation 496964 Page 39 1. Lid tamper connector (SELV) 7. Local Downloader connector (SELV) 2. Wire in comms connector (SELV) 8. Telepho

Strany 92 - 69: Forbikobler Door Locking

3. Installation Page 40 496964 Connecting the Telephone Line Connecting the telephone line directly to the terminals on the internal communicator, or

Strany 93 - 496964 Page 85

3. Installation 496964 Page 41 Fitting a Plug-on Communicator (9851 only) The 9851 control unit can be fitted with a plug-on communicator. To fit

Strany 94 - 74: Level C Entry Time

Contents 496964 Page iii 69: Forbikobler Door Locking ...

Strany 95 - 496964 Page 87

3. Installation Page 42 496964 Fitting a Plug-by Communicator (all models) The control unit can be fitted with a communicator or speech dialler (for

Strany 96 - 78: Level D Entry Time

3. Installation 496964 Page 43 Comms O/P1 (Brown) -ve applied (+ve removed) in alarmComms O/P2 (Orange) -ve applied (+ve removed) in alarmComms O/

Strany 97 - 81 to 84: Output n Type

3. Installation Page 44 496964 Fitting a Battery Fit a rechargeable battery into the back of the case. In the 9751, there is space in the case for a

Strany 98 - Page 90 496964

3. Installation 496964 Page 45 4. Fit the case lid before applying mains power (this also defeats the tamper switch). 5. Apply mains power. The

Strany 99 - 86: Dual Ply Entry Warning

3. Installation Page 46 496964

Strany 100 - Page 92 496964

496964 Page 47 4. PROGRAMMING Entering Programming Mode "3. Installation – Initial Power Up" on page 44 describes how to enter programmin

Strany 101 - 100: Not used

4. Programming Page 48 496964 Summary of Programming Commands Command Key in:0 Country PTT Defaults (page 61) 0YnYn = Country: 0 = UK Y 1 = I

Strany 102 - 102: Not used

4. Programming 496964 Page 49 Command Key in:20 Change Engineer Code (page 68) 20YnnnnYggggYnnnn = New Engineer Code (Code) 7890gggg = New Gu

Strany 103 - 103: Reporting Type

4. Programming Page 50 496964 Command Key in:42 Bell Duration (page 76) 42YnYn = 1 1.5 minutes 2 3 minutes 3 5 minutes 4 10 minutes 5

Strany 104 - 107: Not used

4. Programming 496964 Page 51 Command Key in:66 Forbikobler Partitions – partitioned system only (page 83) 66YnnnnYn = A Assign keypad to Parti

Strany 105 - 110: Download Mode

Contents Page iv 496964 161: Internal Sounder on Confirmed or Unconfirmed Alarm...10

Strany 106 - 113: Answer on One Ring

4. Programming Page 52 496964 Command Key in:81 Output 1 Type (page 89) 81YnYn = Where n is one of: In a single or partitioned system: 00 Bel

Strany 107 - 114: Access Mode

4. Programming 496964 Page 53 Command Key in:105 Static Test Call (page 95) 105Y N nnYN nn = 00 Static off YA nn = Static call daily at nn ho

Strany 108 - 117: Account Number

4. Programming Page 54 496964 Command Key in:151 Plug-by Communications Output 1 (page 108) 151YnnYnn = 00 Not Used 01 Fire Y 02 PA 03 Bu

Strany 109 - 121: Fast Format Channels

4. Programming 496964 Page 55 Command Key in:180 Print Log – 9851 only (page 113) 180YnYn = 0 Off Y 1 On 181 Enable Guard Code (page 113) 1

Strany 110 - 124: Reverse Open/Closed

4. Programming Page 56 496964 Command Key in:198 Fast Format Channel 8 (page 115) 198YnnYn = See Command 191 for a list of options. Default is 0

Strany 111 - 127: Not used

4. Programming 496964 Page 57 Re-entering Programming Mode You can go back into programming mode whenever the system is unset and not in alarm: No

Strany 112 - 131: SIA Report Mode

4. Programming Page 58 496964 Restoring all Factory Default Programming If you wish to restore all factory default options then: 1. Enter programmin

Strany 113

4. Programming 496964 Page 59 Adding and Deleting Tags You can use any industry-standard ISO tag or card with the 934 module. To purchase tags fro

Strany 114

4. Programming Page 60 496964 3. Enter the access code of the user for whom you want to program a tag and press Y. The display shows the user numbe

Strany 115 - 134 to 142: Not used

4. Programming 496964 Page 61 Programming Command Reference 0: Country PTT Defaults Use this command to select the country and PTT defaults; use C

Strany 116 - 144 to 150: Not used

Contents 496964 Page v List of Figures Figure 1. Elements of an Intruder Alert System ...

Strany 117 - 160: Confirmed Alarm Timer

4. Programming Page 62 496964 Enter letters from the keypad one at a time by repeatedly pressing a number key until the display shows the letter you

Strany 118 - Page 110 496964

4. Programming 496964 Page 63 Value Type Description 02 Fire (FR) Smoke or heat detectors connected to FR type zones cause the speakers to give

Strany 119 - 165 to 169: Not used

4. Programming Page 64 496964 Value Type Description 08 Technical (TC) Use this zone type when you want to monitor equipment, for example a freezer,

Strany 120 - 176 to 179: Not used

4. Programming 496964 Page 65 Value Type Description 13 Anti-Mask Zone (AM) Use this zone type for the outputs of detectors that have an Anti-Mas

Strany 121 - 183: Set Display Line 2

4. Programming Page 66 496964 Value Attribute Valid for Description X2 Soak Test (S) Normal Alarm (NA) Entry Route (ER) 24-hour (24) Shock Analyser

Strany 122 - 187 to 190: Not used

4. Programming 496964 Page 67 Value Attribute Valid for Description X7 The meaning of this attribute depends on the zone type: Shock Analyser S

Strany 123 - 496964 Page 115

4. Programming Page 68 496964 Zones and Partitions In a partitioned system, you can assign some zone types to two or more partitions, and some zone t

Strany 124 - 200: Forbikobler Entry Timer

4. Programming 496964 Page 69 21: Zone Configuration This Command allows you to select the wiring type of the zone connectors on the main PCB. 975

Strany 125 - 496964 Page 117

4. Programming Page 70 496964 24: Show Control Unit Account Name An ARC can use Downloader to program an account name into the control unit. While th

Strany 126 - Using a Partitioned System

4. Programming 496964 Page 71 28: Hide Status Display If you select option 0, the keypad displays "Level Set" or "Partn. Set"

Strany 128

4. Programming Page 72 496964 32: Keypads and Partitions If you created a partitioned system during initial power up, this Command enables you to ass

Strany 129 - Common Areas

4. Programming 496964 Page 73 35: First Circuit Lockout If you select option 0 (Lockout), the first zone to activate during the set cycle is ignor

Strany 130 - Page 122 496964

4. Programming Page 74 496964 39: Level/Partition A Exit Mode Use this Command to select the exit mode for Full Set or Partition A. Option 0 Timed.

Strany 131 - 496964 Page 123

4. Programming 496964 Page 75 To unset the system, the user turns the lock switch to "unlocked" (which closes the lock switch contacts

Strany 132 - Page 124 496964

4. Programming Page 76 496964 41: Bell Delay When the system is set and (for example) an intruder violates a zone, the system waits for the programme

Strany 133 - 496964 Page 125

4. Programming 496964 Page 77 44: Level/Partition A Exit Time This Command lets you set the Exit Time for Full Set or Partition A. Option 1 10 sec

Strany 134 - ACPO DD243: 2002 Compliance

4. Programming Page 78 496964 48: Lockout Keypads During Entry This Command provides compliance with DD243: 2002 6.4.5. If you want the user to be ab

Strany 135 - Alarm Filtering

4. Programming 496964 Page 79 51: Set Time and Date The system has an internal clock/calendar, which it uses to date stamp the log print-out. To s

Strany 136 - Page 128 496964

4. Programming Page 80 496964 54: BVVO Supervision (not 9751) If the alarm system must meet BVVO radio supervision requirements, select option 1. In

Strany 137 - 5. TESTING

4. Programming 496964 Page 81 59: External Sounder Tamper This Command specifies which one of two tamper arrangements is used to connect the contr

Strany 138 - Event Log Messages

496964 Page 1 1. INTRODUCTION About this Manual This manual is divided into five chapters: 1. Introduction: this describes the parts of an intrude

Strany 139

4. Programming Page 82 496964 In a partitioned system, the options are: Option 0 Timed. Use this option if Partition B sets after an exit time selec

Strany 140 - 91 to 96: Testing Outputs

4. Programming 496964 Page 83 65: Level/Partition B Exit Time This Command sets the Exit Time for Level or Partition B. Option 1 10 seconds 2 20

Strany 141 - 97: Engineer Walk Test

4. Programming Page 84 496964 68: Forbikobler Door Timer This Command sets the time that the Forbikobler system allows for entry to the building (not

Strany 142 - Page 134 496964

4. Programming 496964 Page 85 71: Level C Entry Route Operation In a single system, this Command specifies how the system treats Entry Route zones

Strany 143 - 496964 Page 135

4. Programming Page 86 496964 73: Level/Partition C Alarm Response This Command sets the Alarm Response for Level or Partition C. In a single system,

Strany 144 - Page 136 496964

4. Programming 496964 Page 87 76: Level/Partition D Exit Mode This Command sets the Exit Mode for Level or Partition D. In a single system, the op

Strany 145 - 496964 Page 137

4. Programming Page 88 496964 77: Level/Partition D Alarm Response This Command sets the Alarm Response for Level or Partition D. In a single system,

Strany 146 - Page 138 496964

4. Programming 496964 Page 89 80: Forbikobler Chime This Command links the bell push on the Forbikobler keypad to the Chime on the system, so that

Strany 147 - 9751/9752/9851

4. Programming Page 90 496964 05 Walk Test: active during both engineer and user Walk Tests and during the time between silencing and resetting the

Strany 148

4. Programming 496964 Page 91 24 Strobe Set C: active for 10 seconds after Partition C is set. 25 Strobe Set D: active for 10 seconds after Part

Komentáře k této Příručce

Žádné komentáře