4. Programming
496964 Page 67
Value Attribute Valid for Description
X7
The meaning of this attribute depends on the zone type:
Shock
Analyser
Sensitivity
Shock
Analyser
(SA)
You can set this attribute only for a
zone of type SA, and only zones 1, 2, 3
and 4 support this type. To set the
sensitivity of a shock sensor zone,
enter a digit in the range 1 (least
sensitive) to 6 (most sensitive). You
must enter the whole sequence; for
example, to set the sensitivity to 3, key
in: X7 and then 3.
Entry Timer
Number
Final Exit
(FE)
Entry Route
(ER)
Forbikobler
(FB)
To select which of the four entry timers
(set up using Commands 201–4, as
described on page 116) are used for
the zone, enter a digit in the range 1 to
4. You must enter the whole sequence;
for example, to select Entry Timer 3,
key in: X7 and then 3.
A Armed in
Level or
Partition A
All When applied, the zone is armed when
the user selects Level or Partition A.
B Armed in
Level or
Partition B
All When applied, the zone is armed when
the user selects Level or Partition B.
C Armed in
Level or
Partition C
All When applied, the zone is armed when
the user selects Level or Partition C.
D Armed in
Level or
Partition D
All When applied, the zone is armed when
the user selects Level or Partition D.
For information on how zones behave in linked partitions, refer to "Common
Areas" on page 121.