Engineering Manual Engineer Menu 2-7
135
Settings Defaulted Grade2 (Grade 3)
Default Value
2-5-1-6-4 Next Service 00:00
2-5-1-6-5 Interval 180 Days
2-1-5-6-6 Call Back Disabled
2-1-5-6-7 Walk Test Alerts Disabled
2-5-2 DigiCom
2-5-2-1 Comms Format Disabled
2-5-2-2 ARC Nos. 1, 2, 3 Blank
2-5-2-3 Account Nos. 1, 2, 3 Blank
2-5-2-4 Dialling Mode Consecutive
2-5-2-5 Restores Enabled
2-5-2-6 CID/SIA Reports Full
2-5-2-7 FF Channels 8 FF Channels
2-5-2-8 Test Call N/A
2-5-2-9 Line Fault Enabled
2-5-4 RS232 Options
2-5-4-1 Baud Rate 38400
2-5-4-2 Remote Modem Disabled
2-6 Shunt Groups
Zones assigned None
Settings Defaulted Grade2 (Grade 3)
Default Value
1-7 Custom Text
1-7-1 Reset Message CALL ENGINEER
TO RESET SYSTEM
1-7-2 Location Text PANEL LOCATION
TEXT NOT SETUP
1-7-3 Printer Title MENVIER
SECURITY M-
RANGE SYSTEM
1-7-4 Remote Reset Msg RING A.R.C FOR
REM. RESET CODE
1-7-5 Banner Text Blank
1-7-6 Group Names Blank
Notes:
1. The control unit ignores this timer until the user
accesses the menu. Once the user selects the menu
the display shows 4 hours and the timer starts from
there on.
2. For Grade 3 requirements, you may need to enable
the Masking attribute on specific zones.
3. There are various options that you can select and still
comply, for example: Final Exit,Exit Terminate, or Lock
Set.
4. 21 is the lowest algorithm that generates 6 digit reset
codes for Grade 3 requirements.
Option 2-7-3-9 – Built In Tests, Equipment, Test Display
Equipment 9
Test Display
[
8888888888888888
8888888888888888
]
Pr e ss w h e n y o u h a ve
finished
[
You can use this option to test the LCD on the keypad you are currently using. The "8" character
should be displayed in each location of the LCD.