Engineer Menu 2-1 Engineering Manual
98
Option 2-1: Viewing Zone Status
[
r
[
]
r
To select zone:
· Press| or ¬ to scroll, or
Pressr to choose a zone on the next network
(e.g. to change 0001 to 1001) or,
Enter zone number (e.g. 2001 )
Press] when you have finished.
Network: device, zone
Zone text
Zone number
Eng 2 Menu 1
View Zones
Panel Zone 1
0001 Healthy
1:011, Remote
1011 Healthy
PIR
2001 Healthy
PIR
9(9) Sup-H Bat-H
1. SELECT ZONE
e.g.
Radio zone status:
current signal strength (lowest previous)
Supervision status
(H=healthy, W=warning, F=failed)
Battery status
(H=healthy. L=low)
Zone status
(A=Activity, zone has operated with the
last seven unset periods. See note 1.)
Note 3:
When you press] the control unit leaves the
previous lowest signal strength unchanged.
If you press[ at this point the control unit
clears the previous lowest signal strength and
updates it with the current signal strength.
Note 1:
You must assign the Activity attribute to a zone
(option 1-1) to make the control panel monitor it.
Note 2:
Press] to view zone resistance (wired FSL zones only)
This option enables you to determine the status of each zone. The zone status conditions and
resistance are shown in the following table for an FSL zone without masking (page 26):
Table 4. Zone Status Conditions and Resistsance for FSL Zones
Condition FSL Resistor Configuration Selected (page 32)
4K7/2K2 1K0/1K0 4K7/4K7 2K2/2K2
Healthy 2.2 KΩ ± 20% 1.0 KΩ ± 20% 4.7 KΩ ± 20% 2.2 KΩ ± 20%
Active 6.9 KΩ ± 20% 2.0 KΩ ± 20% 9.4 KΩ ± 20% 4.4 KΩ ± 20%
Tamper >6.9 K+20% >2.0 K+20% >9.4 K+20% >4.4 K+20%
Shorted <2.2 K- 20% <1.0 K- 20% <4.7 K- 20% <2.2 K- 20%
For an FSL zone with masking:
Healthy = 2.2 KΩ ± 20%
Active = 6.9 KΩ ± 20%
Masked = 4.4 KΩ ± 20%, or 9.1 KΩ ±20%
Tamper = <2.2 K- 20%, or >9.1 K+20%
For double-pole zone:
Healthy = Contacts close circuited and tamper contacts closed circuited
Active = Contacts open circuited and tamper contacts closed circuited