Engineer Menu 2-9 Engineering Manual
150
Follow the advice given for "Why is a keypad or other device not responding correctly?".
Check the resistance of the wiring to the zone sensor: disconnect and short the two zone
cores at the sensor end, then disconnect the same cores at the control unit and measure
the resistance between them. This must not exceed 100 Ohms.
Why is there strange text displayed at a keypad?
Follow the advice given for "Why is a keypad or other device not responding correctly?".
Why is the system indicating that remote keypads or other devices have been removed?
Follow the advice given for "Why is a keypad or other device not responding correctly?".
No keypads are responding. What should I do?
Try the following in order:
1. Check that mains is connected to the control unit and/or a charged battery is
connected.
2. Perform a factory restart – keep the "FACTORY RESTART" pins shorted while applying
power to the control unit. Note: all programming will be lost!
3. Check that the control unit is powered up and that the "HEARTBEAT" LED on the PCB
is flashing once per second. If it is not, the control unit will need to be replaced.
How do I switch on the internal communicator?
Choose a setting other than Disabled in option 2-5-2-1 (page 110), and make sure
that all other options with option 2-5-2 (e.g. 2-5-2-2) have the appropriate
settings. If the phone line is broadband, make sure that the control unit connects via an
ADSL filter.
How do I wire an anti-masking zone?
Refer to the Installation Instructions.
Can TS900 nodes be used on a system?
Yes, they can, but you cannot mix TS900 nodes with MSNodes or MRNodes on any
network. Up to 5 TS900s can be on one network, depending on control unit type.
How can I prevent a user from resetting a confirmed alarm?
Select the appropriate partitions in option 1-3-2-1 (Conf Reset , page 35). Note that
an engineer reset is not required if the user silences the alarm within the Abort Delay
period set in option 1-5-2-12 (page 64).
Can I use TSXNodes on a system?
You can connect one or more TSXNodes provided you group them on their own Network.
I’m having trouble connecting to the ARC over a landline. What can I do?
If the line is shared by a broadband connection then try fitting an approved ADSL filter to
the line. For BT landlines you can fit an ADSL01 module to the later versions of control unit
pcbs (see the M2000 or M800 Installation Instructions).