3. Testing Commands
Page 74 497096, issue 3
97: Engineer Walk Test
This function enables the engineer to test all devices on the system.
1. Enter installer mode.
2. Press 97y
The display shows:
97: Walk Test
3. Open and close each alarm and tamper contact in turn.
The system gives a Chime tone each time you open and close a detector
contact. The display shows: "A: Zone" and the zone number of every
detector you have tested, in sequence and for one second each. If you
also test the tampers on each zone, the display shows the letter "T"
against each zone number.
4. Press X to stop the Walk Test.
Note: The engineer Walk Test enables you to test all zones, including PA zones, zone
tampers, and control unit and bell tampers. The user Walk Test does not enable
you to test tampers or PA, Fire, 24-hour and Technical zones.
199: Display Zone Circuit Resistance
This command lets you step through the zones connected to the control unit,
viewing the resistance of the circuit connected to each. Press 1 (down) and 3
(up) keys to step through the list of zones. The display shows the resistance
of the circuit in ohms, or O/C for open circuit.