2. Programming Commands
497096, issue 3 Page 27
55: Supervision Response
This command specifies how the control unit responds to a reported
supervision failure (as described in Command 54).
Option
0 Supervision response: tamper (default)
1 Supervision response: alarm
2 Supervision response: fault
3 Supervision response: silent
Note: Compliance with PD 6662 / prEN 50131-1: 2004 Grades 1 and 2 (see page 85)
requires option 0. Grade 3 does not permit radio zones.
The response depends on whether the system is set or unset, as well as on
the option selected. The following table shows the possible variations.
Panel UNSET
Option 0 1 2 3
Lights Alert
lamp
Yes Yes Yes Yes
Emits fault tone Yes Yes Yes No
Starts internal
sounder
Yes No No No
Starts external
sounder
No No No No
Sends to ARC
(EN 50131-1)
Tamper None None None
Sends to ARC
(other)
Supervision
Fault
None None None
Records in
event log
Supervision
Fault + Tamper
Supervision
Fault
Supervision
Fault
Supervision
Fault
Panel SET
Option 0 1 2 3
Lights Alert
lamp
No No No No
Emits fault tone No No No No
Starts internal
sounder
Yes Yes No No
Starts external
sounder
Yes Yes No No
Sends to ARC
(EN 50131-1)
Tamper Alarm Supervision
Fault
Supervision
Fault
Sends to ARC
(other)
Supervision
Fault
Supervision
Fault
None None
Records in
event log
Supervision
Fault + Tamper
Supervision
Fault + Alarm
Supervision
Fault
Supervision
Fault