i-on40
Page 9
Zone 1
Zone 2
2K2 EOL
4K7
Alarm contacts
Tamper contacts
2K2 EOL
4K7
Alarm contacts
Tamper contacts
Zone 1
2K2 EOL
4K7
Alarm contacts Alarm contacts
Tamper contacts Tamper contacts
Max 10 devices per c
rcuit (not recommende
)
100 Ohms
Figure 17 Fully Supervised Loop Zone
Wiring
2K2 EOL
Spare
4K7
Black
Red
Blue
To zone •
contacts
Yellow
Figure 18 Example: Wiring Two Door
Contacts to One FSL Zone.
Step 5. Connect Wired
Peripherals
12V +
0V
Tamper In
Tamper Out
Strobe +ve
Strobe -ve
Trigger -ve
+LS
-LS
Figure 19 Connecting Wired Peripherals
The end station pcb provides four
connectors for wired outputs. Outputs 1
and 2 are voltage free relay outputs.
Outputs 3 and 4 are driven by transistors,
and are capable of sinking a maximum
500mA when active. By default outputs 3
and 4 are 0V when active, +12V when
inactive. If you wish to reverse the polarity
of these two outputs use Installer Menu -
Outputs - Wired Outputs – Output 3(4) - Polarity.
Remote Loudspeaker (Optional)
If you wish to add a wired Loudspeaker
unit, then connect it as shown in Figure 19.
Wired External Sounders (Optional)
Wired external sounders differ in their
methods of connection. Figure 19 shows an
example of a general method of using the
outputs to connect a wired sounder.
Note: If you do not wish to connect a wired
external sounder then make sure you link
TR to 0V. This prevents the control unit
reporting Bell Tamper unnecessarily.
Wired Outputs (Optional)
Figure 19 shows an example of using the
wired outputs to drive an indicator LED.