4. Programming
Page 40 496929
0 Low Tone. Timed set with the exit tone fixed at half volume. Use
Command 79 to select the exit time.
1 Instant Set (no exit tone)
2 Silent Set. (Timed Set with no exit tone ).Use Command 79 to
program the Exit time.
3 As A. The exit mode chosen for Level A (whole system) is also
applied to this level.
Note: That the keypads give a double beep confirmation tone at the end of all
setting modes.
77: Level D Alarm Response
Command 77 specifies the alarm response for Level D.
Option
0 Keypad sounders only.
1 Internal sounders and keypad sounders.
2 Local alarm (internal and external sounder only).
3 Full alarm (communication outputs and internal/external sounders).
78: Level D Entry Time
This Command sets the entry time for Level D. See “Programming
Commands” for options.
79: Level D Exit Time
This Command sets the exit time for Level D. See “Programming Commands”
for options.
81, 82, 83, : Output Programming
The system has three transistorised, high current, programmable outputs.
Command 81 programs output 1, Command 82 programs output 2 and,
Command 83 programs output 3. All three Commands take a single following
digit that selects the function.
Note: The outputs are a "pull down” type that provide negative applied control
signals. The outputs float(neither + or -) when inactive, and 0V when
active.